Your home for radio fire alarms, force protection systems, personnel alerting and Addressable fire alarm panels
Email us with your Fire Systems question


BT2-7 Building Transceiver

BT2-7 Building Transceivers provide narrowband radio signaling of alarm and trouble conditions from local fire alarm control systems to the D-700 radio alarm receiving system. Local control panels or supervisory devices that have isolated dry contacts which provide a short for an alarm condition and an open for a trouble condition may be connected directly to the BT2 zone inputs. Interfacing relays may be used to connect other types of outputs.

  • Provides FCC Certified FSK encoded narrowband radio transmission of alarms, troubles and restorations for four zones, expandable up to sixteen zones
  • Expansion modules may be located up to two miles from the BT2-7
  • Communication with the D-700 is supervised and status changes are reported by automatic and manual poll/reply/acknowledge routines
  • 4 watts RF output power (Selected frequencies available with 2 watts RF output power)
  • Microprocessor controlled
  • Includes programmed diagnostic tests
  • LEDs identify BT2 and zone status; defeatable audible alert sounds for alarm and troubles
  • Integral battery disconnect circuitry prevents battery damage due to prolonged discharge
  • Current status is stored in a nonvolatile, transferrable data module
  • Battery fault (low or disconnected battery or abnormal charger output), ac fail and enclosure tamper (optional) conditions and restorations reported with the BT2 number; ac fail reporting may be inhibited


© Monaco Enterprises, 2010. All Rights Reserved.